Pay a Visit to Our Booth in FABTECH
DAYS
0 0
Las Vegas Convention Center
October 21–23 - Booth: C6448
EnglishEnglish

Peak Withstand vs Breaking Current: Two Short-Circuit Ratings That Answer Different Questions

Open a switchgear datasheet and two short-circuit figures sit a few lines apart, both in kA: the rated peak withstand current and the short-circuit breaking current. They look like two versions of one number. They are not. Anyone looking for a short circuit withstand rating tends to meet both, yet only one of them is a withstand rating. The other describes what the circuit-breaker must interrupt. ABB's ZS3.2 and ZS1 data show the difference in real numbers, and on those numbers the peak figure runs at about 2.5 times the breaking figure.
peak withstand current
⏱ ...

Share:

Take a Look at Our Products

Click
Table of Contents

If you’d rather listen than read, feel free to play the audio file below for the rest of this article.

Rated Peak Withstand Current: What the Switchgear Must Survive

The rated peak withstand current belongs to the switchgear and its main conductors, not to the breaker. ABB’s 2001 ZS1 manual makes that plain by calling it the rated impulse current of the main conductor: 125 kA at 12 kV.

It is the highest instantaneous short-circuit current the installation is rated to withstand. At that instant the electrodynamic forces between conductors are at their greatest, so this is a mechanical rating as much as an electrical one.

That puts the figure on the busbars, their supports and joints, and everything else fixed in the current path. The breaker can be the best in the line-up and still add nothing to it.

ABB’s ZS3.2 table gives up to 80 kA, with 100 kA available on request.

On projects, the common mistake is to read the breaker’s datasheet and assume the panel matches it. Check the peak figure against the calculated peak fault current as a separate line item.

Ratings like these are defined and tested under recognised standards, not left to the manufacturer’s judgement. For the full picture, see our overview of switchgear standards and how they apply to busbar systems.

Short Circuit Breaking Current: What the Breaker Must Interrupt

The short circuit breaking current is attached to one device, the circuit-breaker: it is the fault current that breaker is rated to interrupt. ABB’s ZS3.2 lists up to 31.5 kA, with 40 kA on request.

ABB spells out the ownership. Both manuals list the breaking value “of the circuit-breaker”, a qualifier the peak row never carries. In ZS1 the figures are 50 kA at 12 kV and 40 kA at 17.5 kV.

Interrupting is a different job from withstanding. The breaker has to open and clear the fault, while the conductors only have to hold together as it flows. How the breaker does that is a separate subject.

That difference is why a strong breaker cannot rescue weak busbars. A breaker that clears the fault still lets the peak pass through the conductors first.

A breaker is one layer of a wider protection scheme, and it only acts after a fault has begun. Our guide to overcurrent protection methods explains how the layers fit together.

Recommended machine

HBC-C200

Cuts, punches and bends the exact copper and aluminium bar sizes in this guide — up to 120 × 12 mm, three stations at once.

120 × 12 mm

3 power packs

Cut · Punch · Bend

peak withstand current

Side by Side: Real Values

Across ABB’s three data sets, dividing the peak figure by the breaking figure gives about 2.5 every time.

Design Rated voltage Rated peak withstand current Breaking current (circuit-breaker) Short-time current Peak ÷ breaking
ZS3.2 36/40.5 kV Up to 80 kA (100 kA on request) Up to 31.5 kA (40 kA on request) 31.5 kA, 3 s ≈2.5
ZS1 12 kV 125 kA 50 kA 50 kA, 3 s 2.5
ZS1 17.5 kV 100 kA 40 kA 40 kA, 3 s 2.5

Treat that ratio as arithmetic on ABB’s values, not as a design rule. ABB publishes the figures without saying how one relates to the other, so no rule is claimed here.

For a specifier, the useful habit is to check each column against its own requirement. The peak figure goes against the calculated peak fault current, and the breaking figure against the fault current the breaker must clear.

You can also save a copy for later, which is helpful if you plan to return to this more than once.

Comparing ratings is only useful when the assembly itself has been verified against them. Read our guide to IEC 61439 verification to see what that involves.

Where Else These Numbers Matter

Three more things have to be read against these figures: the instrument transformers, the earthing switch and the short-time rating.

ABB footnotes its withstand ratings with a warning: instrument transformers have their own short-circuit withstand capability, which needs checking separately. In ZS3.2 it sits on both the peak and short-time rows; in ZS1, on the short-time row.

The ZS3.2 earthing switch has a making capacity of 62.5 kA, with an 80 kA design in preparation, so set it beside the panel’s 80 kA peak figure before specifying.

The short-time current rating sits alongside both, and its duration has its own article.

The earthing switch closes onto a path that must carry fault current safely to ground. Our article on earthing systems shows how that path is designed.

HBC-A120

Recommended machine

HBC-A120

Cuts, punches and bends the exact copper and aluminium bar sizes in this guide — up to 120 × 12 mm, three stations at once.

120 × 12 mm

3 power packs

Cut · Punch · Bend

Conclusion about peak withstand current

Breaking current asks whether the breaker clears the fault; the rated peak withstand current asks whether the busbars survive it. That is why supports and joints are made to drawing. See our busbar processing machines.

Safe ratings start with busbars made to a controlled, compliant process. Learn more about busbar manufacturing compliance and what it covers.

FAQs about peak withstand current

What is rated peak withstand current?

The highest instantaneous short-circuit current the switchgear and its main conductors are rated to withstand. ABB's ZS3.2 lists up to 80 kA.

What is short-circuit breaking current?

The fault current the circuit-breaker is rated to interrupt. ABB lists it against the breaker: up to 31.5 kA on ZS3.2.

Why is peak withstand current higher than breaking current?

It rates the instantaneous peak the conductors must survive, not the current the breaker interrupts. On ABB's figures it is about 2.5 times the breaking figure.

Which device carries the breaking rating?

The circuit-breaker. The peak withstand rating belongs to the switchgear and its main conductors instead.

Do instrument transformers share the switchgear rating?

Not automatically. ABB's footnote says to check their short-circuit withstand capability separately.

How many kA ratings does a switchgear datasheet carry?

ABB's carry several: peak withstand, breaking, short-time, earthing switch making capacity and internal arc. Each rates a different part or event.

What goes wrong if you specify only the breaking current?

The breaker may clear the fault, yet nothing confirms the conductors and instrument transformers survive its peak. Check those ratings too.

What does "on request" mean in ABB's ZS3.2 values?

Higher ratings are available to order: 100 kA peak instead of 80 kA, and 40 kA breaking instead of 31.5 kA.

Rate this article

Choose a rating from 1 to 5 stars.

No ratings yet

0 Comments

No comments yet. Be the first to comment.

Leave a comment

Download
Catalog
2026

Download

Subscribe to Newsletter

WhatsApp WhatsApp Support

Fill the Form to Contact Our Specialists Directly

"*" indicates required fields

This field is for validation purposes and should be left unchanged.